ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407055

Federal Type:

NTNC

Water System Name:

USAF GILA BEND

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
CE02227 1074 ANTIMONY, TOTAL 2022-03-16 EPDS001 < MRL 0.001 MG/L .006 MG/L 2022-01-01
2024-12-31
CE02227 1005 ARSENIC 2022-03-16 EPDS001 0.030  MG/L .01 MG/L
CE02227 1010 BARIUM 2022-03-16 EPDS001 0.013  MG/L 2 MG/L 2022-01-01
2024-12-31
CE02227 1075 BERYLLIUM, TOTAL 2022-03-16 EPDS001 < MRL 0.001 MG/L .004 MG/L 2022-01-01
2024-12-31
CE02227 1015 CADMIUM 2022-03-16 EPDS001 < MRL 0.001 MG/L .005 MG/L 2022-01-01
2024-12-31
CE02227 1020 CHROMIUM 2022-03-16 EPDS001 0.0079  MG/L .1 MG/L 2022-01-01
2024-12-31
CE02227 1024 CYANIDE 2022-03-16 EPDS001 < MRL 0.01 MG/L .2 MG/L 2022-01-01
2024-12-31
CE02227 1025 FLUORIDE 2022-03-16 EPDS001 1.8  MG/L 4 MG/L
CE02227 1035 MERCURY 2022-03-16 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2022-01-01
2024-12-31
CE02227 1036 NICKEL 2022-03-16 EPDS001 0.0021  MG/L 2022-01-01
2024-12-31
CE02227 1040 NITRATE 2022-03-16 EPDS001 5.10  MG/L 10 MG/L 2022-01-01
2022-03-31
CE02227 1038 NITRATE-NITRITE 2022-03-16 EPDS001 5.10  MG/L 10 MG/L
CE02227 1041 NITRITE 2022-03-16 EPDS001 < MRL 0.01 MG/L 1 MG/L 2022-01-01
2030-12-31
CE02227 1045 SELENIUM 2022-03-16 EPDS001 < MRL 0.002 MG/L .05 MG/L 2022-01-01
2024-12-31
CE02227 1052 SODIUM 2022-03-16 EPDS001 320  MG/L 3000 MG/L
CE02227 1085 THALLIUM, TOTAL 2022-03-16 EPDS001 < MRL 0.001 MG/L .002 MG/L 2022-01-01
2024-12-31