ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0413052

Federal Type:

C

Water System Name:

HUMBOLDT WATER SYSTEM

Primary Source:

GW

Principal County Served:

YAVAPAI

System Status:

A - MAP

Comments:

Activity Date:

1932-01-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
93-0443 1005 ARSENIC 1993-06-24 EPDS001 .18  MG/L .01 MG/L
93-0443 1010 BARIUM 1993-06-24 EPDS001 < MRL 0.5 MG/L 2 MG/L
93-0443 1015 CADMIUM 1993-06-24 EPDS001 .001  MG/L .005 MG/L
93-0443 1017 CHLORIDE 1993-06-24 EPDS001 17  MG/L 250 MG/L
93-0443 1020 CHROMIUM 1993-06-24 EPDS001 .01  MG/L .1 MG/L
93-0443 1022 COPPER, FREE 1993-06-24 EPDS001 < MRL 0.05 MG/L 1.3 MG/L
93-0443 1028 IRON 1993-06-24 EPDS001 < MRL 0.01 MG/L .3 MG/L
93-0443 1030 LEAD 1993-06-24 EPDS001 < MRL 0.005 MG/L
93-0443 1032 MANGANESE 1993-06-24 EPDS001 < MRL 0.05 MG/L .05 MG/L
93-0443 1035 MERCURY 1993-06-24 EPDS001 .001  MG/L .002 MG/L
93-0443 1040 NITRATE 1993-06-24 EPDS001 2.9  MG/L 10 MG/L
93-0443 1045 SELENIUM 1993-06-24 EPDS001 < MRL 0.005 MG/L .05 MG/L
93-0443 1050 SILVER 1993-06-24 EPDS001 < MRL 0.005 MG/L .1 MG/L
93-0443 1052 SODIUM 1993-06-24 EPDS001 114  MG/L 3000 MG/L
93-0443 1055 SULFATE 1993-06-24 EPDS001 31  MG/L 250 MG/L
93-0443 1095 ZINC 1993-06-24 EPDS001 < MRL 0.05 MG/L 5 MG/L