The overflow pipes for the 100,000 gallon storage tank, the 1.2 MG storage tank at the well 71 site, and the 1.4 MG storage tank are not protected with a #16 non-corrodible mesh.
12-05-2017
SO
REC
9 -<1:100,000
Remove threads from raw water sample taps.
12-05-2017
OT
REC
15 -15
For the emergency operations plan, add the system name, ADEQ contacts, and notice procedures for regulatory agencies, news media, and users.
12-05-2017
SO
MIN
There is no raw water sample tap at well 72 (55-626038).