ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0409004

Federal Type:

C

Water System Name:

ARIZONA WATER CO - OVERGAARD

Primary Source:

GW

Principal County Served:

NAVAJO

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
21F1456-01 1074 ANTIMONY, TOTAL 2021-06-09 EPDS003 < MRL 0.0005 MG/L .006 MG/L 2021-01-01
2023-12-31
21F1456-01 1005 ARSENIC 2021-06-09 EPDS003 0.0073  MG/L .01 MG/L 2021-04-01
2021-06-30
21F1456-01 1010 BARIUM 2021-06-09 EPDS003 0.28  MG/L 2 MG/L 2021-01-01
2023-12-31
21F1456-01 1075 BERYLLIUM, TOTAL 2021-06-09 EPDS003 < MRL 0.002 MG/L .004 MG/L 2021-01-01
2023-12-31
21F1456-01 1015 CADMIUM 2021-06-09 EPDS003 < MRL 0.0001 MG/L .005 MG/L 2021-01-01
2023-12-31
21F1456-01 1020 CHROMIUM 2021-06-09 EPDS003 < MRL 0.005 MG/L .1 MG/L 2021-01-01
2023-12-31
21F1456-01 1024 CYANIDE 2021-06-09 EPDS003 < MRL 0.01 MG/L .2 MG/L 2021-01-01
2023-12-31
21F1456-01 1025 FLUORIDE 2021-06-09 EPDS003 < MRL 0.1 MG/L 4 MG/L 2021-01-01
2023-12-31
21F1456-01 1035 MERCURY 2021-06-09 EPDS003 < MRL 0.0002 MG/L .002 MG/L 2021-01-01
2023-12-31
21F1456-01 1036 NICKEL 2021-06-09 EPDS003 < MRL 0.02 MG/L 2021-01-01
2023-12-31
21F1456-01 1045 SELENIUM 2021-06-09 EPDS003 0.002  MG/L .05 MG/L 2021-01-01
2023-12-31
21F1456-01 1052 SODIUM 2021-06-09 EPDS003 4.4  MG/L 3000 MG/L 2021-01-01
2023-12-31
21F1456-01 1085 THALLIUM, TOTAL 2021-06-09 EPDS003 < MRL 0.0005 MG/L .002 MG/L 2021-01-01
2023-12-31