ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407695

Federal Type:

C

Water System Name:

EPCOR - AGUA FRIA

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1986-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
6060112-04 1074 ANTIMONY, TOTAL 2016-06-01 EPDS004 < MRL 0.0005 MG/L .006 MG/L 2014-01-01
2016-12-31
6060112-04 1005 ARSENIC 2016-06-01 EPDS004 0.0014  MG/L .01 MG/L 2014-01-01
2016-12-31
6060112-04 1010 BARIUM 2016-06-01 EPDS004 0.14  MG/L 2 MG/L 2014-01-01
2016-12-31
6060112-04 1075 BERYLLIUM, TOTAL 2016-06-01 EPDS004 < MRL 0.002 MG/L .004 MG/L 2014-01-01
2016-12-31
6060112-04 1015 CADMIUM 2016-06-01 EPDS004 < MRL 0.0001 MG/L .005 MG/L 2014-01-01
2016-12-31
6060112-04 1020 CHROMIUM 2016-06-01 EPDS004 < MRL 0.005 MG/L .1 MG/L 2014-01-01
2016-12-31
6060112-04 1024 CYANIDE 2016-06-01 EPDS004 < MRL 0.01 MG/L .2 MG/L 2014-01-01
2016-12-31
6060112-04 1025 FLUORIDE 2016-06-01 EPDS004 0.28  MG/L 4 MG/L 2014-01-01
2016-12-31
6060112-04 1035 MERCURY 2016-06-01 EPDS004 < MRL 0.0002 MG/L .002 MG/L 2014-01-01
2016-12-31
6060112-04 1036 NICKEL 2016-06-01 EPDS004 < MRL 0.02 MG/L 2014-01-01
2016-12-31
6060112-04 1040 NITRATE 2016-06-01 EPDS004 0.23  MG/L 10 MG/L 2016-01-01
2016-12-31
6060112-04 1038 NITRATE-NITRITE 2016-06-01 EPDS004 0.23  MG/L 10 MG/L
6060112-04 1041 NITRITE 2016-06-01 EPDS004 < MRL 0.1 MG/L 1 MG/L 2011-01-01
2019-12-31
6060112-04 1045 SELENIUM 2016-06-01 EPDS004 0.0032  MG/L .05 MG/L 2014-01-01
2016-12-31
6060112-04 1052 SODIUM 2016-06-01 EPDS004 99  MG/L 3000 MG/L 2014-01-01
2016-12-31
6060112-04 1085 THALLIUM, TOTAL 2016-06-01 EPDS004 < MRL 0.0005 MG/L .002 MG/L 2014-01-01
2016-12-31