ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407695

Federal Type:

C

Water System Name:

EPCOR - AGUA FRIA

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1986-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
6060444-02I 1074 ANTIMONY, TOTAL 2016-06-06 EPDS008 < MRL 0.0005 MG/L .006 MG/L 2014-01-01
2016-12-31
6060444-02I 1005 ARSENIC 2016-06-06 EPDS008 0.0012  MG/L .01 MG/L 2014-01-01
2016-12-31
6060444-02I 1010 BARIUM 2016-06-06 EPDS008 0.13  MG/L 2 MG/L 2014-01-01
2016-12-31
6060444-02I 1075 BERYLLIUM, TOTAL 2016-06-06 EPDS008 < MRL 0.002 MG/L .004 MG/L 2014-01-01
2016-12-31
6060444-02I 1015 CADMIUM 2016-06-06 EPDS008 < MRL 0.0001 MG/L .005 MG/L 2014-01-01
2016-12-31
6060444-02I 1020 CHROMIUM 2016-06-06 EPDS008 < MRL 0.005 MG/L .1 MG/L 2014-01-01
2016-12-31
6060444-02I 1024 CYANIDE 2016-06-06 EPDS008 < MRL 0.01 MG/L .2 MG/L 2014-01-01
2016-12-31
6060444-02I 1025 FLUORIDE 2016-06-06 EPDS008 0.29  MG/L 4 MG/L 2014-01-01
2016-12-31
6060444-02I 1035 MERCURY 2016-06-06 EPDS008 < MRL 0.0002 MG/L .002 MG/L 2014-01-01
2016-12-31
6060444-02I 1036 NICKEL 2016-06-06 EPDS008 < MRL 0.02 MG/L 2014-01-01
2016-12-31
6060444-02I 1040 NITRATE 2016-06-06 EPDS008 < MRL 0.2  10 MG/L 2016-04-01
2016-06-30
6060444-02I 1041 NITRITE 2016-06-06 EPDS008 < MRL 0.1 MG/L 1 MG/L 2014-01-01
2022-12-31
6060444-02I 1045 SELENIUM 2016-06-06 EPDS008 0.0027  MG/L .05 MG/L 2014-01-01
2016-12-31
6060444-02I 1052 SODIUM 2016-06-06 EPDS008 98  MG/L 3000 MG/L 2014-01-01
2016-12-31
6060444-02I 1085 THALLIUM, TOTAL 2016-06-06 EPDS008 < MRL 0.0005 MG/L .002 MG/L 2014-01-01
2016-12-31