ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0409004

Federal Type:

C

Water System Name:

ARIZONA WATER CO - OVERGAARD

Primary Source:

GW

Principal County Served:

NAVAJO

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
940166182 1005 ARSENIC 1994-01-10 EPDS004 < MRL 0.006 MG/L .01 MG/L
940166182 1010 BARIUM 1994-01-10 EPDS004 < MRL 0.1 MG/L 2 MG/L
940166182 1015 CADMIUM 1994-01-10 EPDS004 .01  MG/L .005 MG/L
940166182 1017 CHLORIDE 1994-01-10 EPDS004 1.2  MG/L 250 MG/L
940166182 1020 CHROMIUM 1994-01-10 EPDS004 < MRL 0.002 MG/L .1 MG/L
940166182 1022 COPPER, FREE 1994-01-10 EPDS004 .03  MG/L 1.3 MG/L
940166182 1025 FLUORIDE 1994-01-10 EPDS004 .16  MG/L 4 MG/L
940166182 1028 IRON 1994-01-10 EPDS004 .77  MG/L .3 MG/L
940166182 1030 LEAD 1994-01-10 EPDS004 .008  MG/L
940166182 1032 MANGANESE 1994-01-10 EPDS004 .058  MG/L .05 MG/L
940166182 1035 MERCURY 1994-01-10 EPDS004 < MRL 0.0002 MG/L .002 MG/L
940166182 1040 NITRATE 1994-01-10 EPDS004 .18  MG/L 10 MG/L
940166182 1045 SELENIUM 1994-01-10 EPDS004 .01  MG/L .05 MG/L
940166182 1050 SILVER 1994-01-10 EPDS004 < MRL 0.01 MG/L .1 MG/L
940166182 1052 SODIUM 1994-01-10 EPDS004 8.8  MG/L 3000 MG/L
940166182 1055 SULFATE 1994-01-10 EPDS004 304  MG/L 250 MG/L
940166182 1095 ZINC 1994-01-10 EPDS004 .13  MG/L 5 MG/L