ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407101

Federal Type:

C

Water System Name:

TOLLESON CITY OF

Primary Source:

SWP

Principal County Served:

MARICOPA

System Status:

A - MAP

Comments:

Activity Date:

1978-04-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
1-903-334-01I 1074 ANTIMONY, TOTAL 1999-03-23 EPDS008 < MRL 0.001 MG/L .006 MG/L
1-903-334-01I 1005 ARSENIC 1999-03-23 EPDS008 .003  MG/L .01 MG/L
1-903-334-01I 1010 BARIUM 1999-03-23 EPDS008 .071  MG/L 2 MG/L
1-903-334-01I 1075 BERYLLIUM, TOTAL 1999-03-23 EPDS008 < MRL 0.001 MG/L .004 MG/L
1-903-334-01I 1015 CADMIUM 1999-03-23 EPDS008 < MRL 0.0001 MG/L .005 MG/L
1-903-334-01I 1020 CHROMIUM 1999-03-23 EPDS008 < MRL 0.001 MG/L .1 MG/L
1-903-334-01I 1035 MERCURY 1999-03-23 EPDS008 < MRL 0.0001 MG/L .002 MG/L
1-903-334-01I 1036 NICKEL 1999-03-23 EPDS008 < MRL 0.005 MG/L
1-903-334-01I 1040 NITRATE 1999-03-23 EPDS008 .24  MG/L 10 MG/L
1-903-334-01I 1041 NITRITE 1999-03-23 EPDS008 < MRL 0.05 MG/L 1 MG/L
1-903-334-01I 1045 SELENIUM 1999-03-23 EPDS008 < MRL 0.005 MG/L .05 MG/L
1-903-334-01I 1052 SODIUM 1999-03-23 EPDS008 120  MG/L 3000 MG/L
1-903-334-01I 1085 THALLIUM, TOTAL 1999-03-23 EPDS008 < MRL 0.001 MG/L .002 MG/L