ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407100

Federal Type:

C

Water System Name:

TEMPE CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1978-05-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
94-2081 1005 ARSENIC 1994-06-13 EPDS200 .0045  MG/L .01 MG/L
94-2081 1015 CADMIUM 1994-06-13 EPDS200 < MRL 0.001 MG/L .005 MG/L
94-2081 1017 CHLORIDE 1994-06-13 EPDS200 93  MG/L 250 MG/L
94-2081 1020 CHROMIUM 1994-06-13 EPDS200 < MRL 0.0025 MG/L .1 MG/L
94-2081 1022 COPPER, FREE 1994-06-13 EPDS200 < MRL 0.1 MG/L 1.3 MG/L
94-2081 1025 FLUORIDE 1994-06-13 EPDS200 .8  MG/L 4 MG/L
94-2081 1028 IRON 1994-06-13 EPDS200 < MRL 0.05 MG/L .3 MG/L
94-2081 1030 LEAD 1994-06-13 EPDS200 < MRL 0.0025 MG/L
94-2081 1032 MANGANESE 1994-06-13 EPDS200 < MRL 0.05 MG/L .05 MG/L
94-2081 1040 NITRATE 1994-06-13 EPDS200 < MRL 0.1 MG/L 10 MG/L
94-2081 1038 NITRATE-NITRITE 1994-06-13 EPDS200 < MRL 0.1 MG/L 10 MG/L
94-2081 1041 NITRITE 1994-06-13 EPDS200 < MRL 0.1 MG/L 1 MG/L
94-2081 1045 SELENIUM 1994-06-13 EPDS200 < MRL 0.005 MG/L .05 MG/L
94-2081 1050 SILVER 1994-06-13 EPDS200 < MRL 0.025 MG/L .1 MG/L
94-2081 1052 SODIUM 1994-06-13 EPDS200 63.7  MG/L 3000 MG/L
94-2081 1055 SULFATE 1994-06-13 EPDS200 58  MG/L 250 MG/L
94-2081 1095 ZINC 1994-06-13 EPDS200 < MRL 0.1 MG/L 5 MG/L