ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407100

Federal Type:

C

Water System Name:

TEMPE CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1978-05-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
BE03757 1074 ANTIMONY, TOTAL 1999-04-20 EPDS200 < MRL 0.003 MG/L .006 MG/L
BE03757 1005 ARSENIC 1999-04-20 EPDS200 < MRL 0.03 MG/L .01 MG/L
BE03757 1010 BARIUM 1999-04-20 EPDS200 .09  MG/L 2 MG/L
BE03757 1075 BERYLLIUM, TOTAL 1999-04-20 EPDS200 < MRL 0.002 MG/L .004 MG/L
BE03757 1015 CADMIUM 1999-04-20 EPDS200 < MRL 0.002 MG/L .005 MG/L
BE03757 1020 CHROMIUM 1999-04-20 EPDS200 < MRL 0.01 MG/L .1 MG/L
BE03757 1035 MERCURY 1999-04-20 EPDS200 < MRL 0.0002 MG/L .002 MG/L
BE03757 1036 NICKEL 1999-04-20 EPDS200 < MRL 0.01 MG/L
BE03757 1040 NITRATE 1999-04-20 EPDS200 1.06  MG/L 10 MG/L
BE03757 1041 NITRITE 1999-04-20 EPDS200 < MRL 0.01 MG/L 1 MG/L
BE03757 1045 SELENIUM 1999-04-20 EPDS200 < MRL 0.02 MG/L .05 MG/L
BE03757 1052 SODIUM 1999-04-20 EPDS200 150  MG/L 3000 MG/L
BE03757 1055 SULFATE 1999-04-20 EPDS200 151  MG/L 250 MG/L
BE03757 1085 THALLIUM, TOTAL 1999-04-20 EPDS200 < MRL 0.001 MG/L .002 MG/L